On-site generation · gas
Gas turbine, cut open
Drag to orbit · scroll to zoom · click any part
Every component, inlet to stack
Air path
Inlet filter houseCleans and quiets a river of air before the compressor.+
A turbine this size swallows several hundred kilograms of air every second. The filter house strips dust and salt, a silencer cuts noise, and optional evaporative coolers or chillers cool the air on hot days to recover power.
- Airflow
- ≈600–1,000 kg/s
- Filtration
- Multi-stage, up to EPA/HEPA (E12)
- Pressure drop
- ≈0.5–1 kPa
- Options
- Inlet chilling or fogging, anti-icing
Axial compressorRows of spinning blades squeeze air about 20 times.+
Alternating rows of rotating blades and fixed vanes each raise pressure a little. Variable inlet guide vanes at the front adjust airflow for part load. The compressor absorbs roughly half of the power the turbine makes.
- Stages
- ≈14–21
- Pressure ratio
- ≈20–24 : 1
- Exit temperature
- ≈450–500 °C
- Speed
- 3,600 rpm (60 Hz, direct drive)
- Power absorbed
- ≈50% of turbine output
Hot section
Combustion systemA ring of cans where natural gas burns in compressed air.+
Compressed air and fuel mix in a ring of combustor cans. Dry low-NOx designs premix lean so the flame stays cooler and makes less nitrogen oxide. Newer units can burn hydrogen blends.
- Layout
- Can-annular, ≈12–16 cans
- Firing temperature
- ≈1,400–1,600 °C
- NOx
- ≈9–25 ppm (DLN), lower with SCR
- Fuel
- Natural gas; ≈30–50% H₂ blends offered
- Fuel flow
- ≈15–20 kg/s at full load
Turbine sectionHot gas spins four stages of superalloy blades.+
The hot gas expands through four stages, spinning the shaft. First-stage blades run in gas hotter than their own melting point, survived only by internal air cooling channels, film cooling holes and ceramic thermal-barrier coatings.
- Stages
- 4
- Blade material
- Single-crystal nickel superalloy
- Coatings
- Ceramic thermal barrier (YSZ)
- Cooling
- Internal passages + film holes
- Inspection
- Hot gas path ≈every 24,000–32,000 h
Exhaust diffuser and stackStill about 600 °C, carrying roughly 60% of the fuel energy out.+
The diffuser slows the exhaust to recover pressure. In simple cycle it leaves through a stack; in combined cycle a heat recovery steam generator turns that heat into steam for a second turbine, lifting efficiency from about 43% to over 63%.
- Exhaust temperature
- ≈600–650 °C
- Simple-cycle efficiency
- ≈41–44% (LHV)
- Combined-cycle efficiency
- ≈63–64% (LHV)
- Stack height
- ≈20–40 m
Generator and grid
Rotor and bearingsOne solid shaft from compressor to turbine to generator.+
A bolted stack of forged discs forms a single rotor weighing on the order of 100 tonnes, riding on oil-film journal bearings and a thrust bearing that holds it in place axially.
- Speed
- 3,600 rpm
- Rotor mass
- ≈80–120 t
- Bearings
- Tilting-pad journal + thrust
- Monitoring
- Vibration, temperature, axial position
GeneratorTurns shaft power into 60 Hz electricity at about 20 kV.+
A two-pole synchronous generator spins with the turbine at grid frequency. Large units are hydrogen-cooled because hydrogen carries heat far better than air with less drag.
- Output
- ≈300–550 MW (H-class simple cycle)
- Voltage
- ≈18–24 kV
- Cooling
- Hydrogen (large units) or air
- Efficiency
- ≈98.8–99%
- Start
- Static frequency converter spins it up
Generator step-up transformerLifts ≈20 kV to transmission voltage.+
Connects the generator through isolated-phase bus to the grid or straight to a campus substation. At a behind-the-meter AI campus this may step to 34.5 kV for site distribution instead.
- Rating
- ≈350–600 MVA
- Ratio
- ≈20 kV → 230–500 kV (or 34.5 kV on site)
- Cooling
- ONAN/ONAF/ODAF
Auxiliaries
Fuel gas skidFilters, heats and meters gas to the right pressure.+
Pipeline gas is filtered, heated to stay above its dew point and controlled through stop and control valves. H-class units need high fuel pressure, often requiring a compressor at the site.
- Supply pressure
- ≈3–4.5 MPa (≈450–650 psig)
- Flow
- ≈2–3 million m³ per day at full load
- Safety
- Double block-and-bleed valves
Lube oil systemKeeps every bearing floating on a film of oil.+
A reservoir, pumps, coolers and filters feed oil to every bearing. An emergency DC pump keeps oil flowing while the rotor coasts down if all AC power is lost.
- Reservoir
- ≈15,000–30,000 L
- Pumps
- AC main, AC standby, DC emergency
- Turning gear
- Rotates the shaft slowly while cooling
Control and starting packageBrains, fire protection and the starting system.+
The control system manages start, load and protection. A static starter runs the generator as a motor to bring the shaft up to speed; the unit can reach full load in about 10–30 minutes. A CO₂ system protects the enclosure.
- Start to full load
- ≈10–30 min (aeroderivatives ≈5–10)
- Ramp rate
- ≈50–90 MW/min
- Fire protection
- CO₂ or water mist in enclosure
Typical ranges for heavy-duty F/H-class units from published OEM data (GE 7HA, Siemens Energy SGT6-9000HL, Mitsubishi M501J class) and EPRI/DOE references. A specific machine differs. Not an engineering document.